SECTION 6: DIESEL-BURNER OVERVIEW
Figure 26
The Diesel-Burner will continue to produce heat in this manner until it is
switched off either manually or by the VDC Control Thermostat, which oc-
curs when the coolant temperature in the Aqua Hot’s Boiler Tank Reaches
200 (+/- 5) degrees Fahrenheit.
NOTE: Whenever the Diesel-Burner is switched off by the VDC Con-
trol Thermostat, it will automatically be reactivated once the Aqua-Hot
Boiler Tank’s coolant reaches the preset termperature of approximately
175 (+/-) 5 degrees Fahrenheit.