Aqua-Hot AHE-200-02S-24 VDC Installation Guide Page 30

  • Download
  • Add to my manuals
  • Print
  • Page
    / 59
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 29
3.2.3. Earthing
The following basic issues need to be considered when installing a frequency converter, so as to
obtain electromagnetic compatibility (EMC).
Safety earthing: Please note that the frequency converter has a high leakage current and
must be earthed appropriately for safety reasons. Apply local safety regulations.
High-frequency earthing: Keep the earth wire connections as short as possible.
Connect the different earth systems at the lowest possible conductor impedance. The lowest pos-
sible conductor impedance is obtained by keeping the conductor as short as possible and by using
the greatest possible surface area.
The metal cabinets of the different devices are mounted on the cabinet rear plate using the lowest
possible HF impedance. This avoids having different HF voltages for the individual devices and
avoids the risk of radio interference currents running in connection cables that may be used be-
tween the devices. The radio interference will have been reduced.
In order to obtain a low HF impedance, use the fastening bolts of the devices as HF connection
to the rear plate. It is necessary to remove insulating paint or similar from the fastening points.
3.2.4. Extra Protection (RCD)
ELCB relays, multiple protective earthing or earthing can be used as extra protection, provided
that local safety regulations are complied with.
In the case of an earth fault, a DC content may develop in the faulty current.
If ELCB relays are used, local regulations must be observed. Relays must be suitable for protection
of 3-phase equipment with a bridge rectifier and for a brief discharge on power-up.
See also the section
Special Conditions
in the relevant Design Guide.
3.2.5. RFI Switch
Mains supply isolated from earth:
If the frequency converter is supplied from an isolated mains source (IT mains, floating delta and
grounded delta) or TT/TN-S mains with grounded leg, the RFI switch is recommended to be turned
off (OFF)
1)
. For further reference, see IEC 364-3. In case optimum EMC performance is needed,
parallel motors are connected or the motor cable length is above 25 m, it is recommended to set
the switch in ON position.
In OFF position, the internal RFI capacities (filter capacitors) between the chassis and the inter-
mediate circuit are cut off to avoid damage to the intermediate circuit and to reduce the earth
capacity currents (according to IEC 61800-3).
Please also refer to the application note
VLT on IT mains
, MN.90.CX.02. It is important to use
isolation monitors that are capable for use together with power electronics (IEC 61557-8).
The RFI switch is not to be operated with mains connected to the unit. Check that
the mains supply has been disconnected before operating the RFI switch.
Open RFI switch is only allowed at factory set switching frequencies.
3. Installation
VLT
®
5000/6000/8000
High Power Installation Guide
30
MI.90.J2.02 - VLT
®
is a registered Danfoss trademark
3
Page view 29
1 2 ... 25 26 27 28 29 30 31 32 33 34 35 ... 58 59

Comments to this Manuals

No comments