If the temperature of the brake resistor gets too high and the thermal switch drops
out, the frequency converter will stop braking. The motor will start coasting.
A KLIXON switch must be installed that is `normally closed'. If this function is not
used, 106 and 104 must be short-circuited together.
3.2.11. Load Sharing
(Only extended with typecode EB, EX, DE, DX).
Terminal
No.
Function
88, 89 Loadsharing
The connection cable must be screened and the max. length from the frequency converter to the
DC bar is 25 metres (82 feet).
Load sharing enables linking of the DC intermediate circuits of several frequency converters.
Please note that voltages up to 1099 V DC may occur on the terminals.
Load sharing calls for extra equipment. For further information please consult Load-
sharing Instructions MI.50.NX.XX.
Illustration 3.38: Load sharing connection.
3.2.12. Shielding against Electrical Noise
Before mounting the mains power cable,
mount the EMC metal cover to ensure best
EMC performance.
NOTE: The EMC metal cover is only included
in units with an RFI filter.
VLT
®
5000/6000/8000
High Power Installation Guide
3. Installation
MI.90.J2.02 - VLT
®
is a registered Danfoss trademark
33